Application

SF6 gas Insulated RMU

SF6 gas Insulated Switchgear

Technical Data

Nominal size in mm

Φ64

Accuracy class

At 20℃:1.0 or 1.6;-40℃ to +60℃:2.5

Scale ranges

0-2bar (abs.) or -1~6bar

Permissible temperature

Ambient: -40~+60℃, relative humidity≤95%RH

Contact type

Magnetic snap-action switch (Maximum 2 groups, Maximum 3 groups)

Insulation properties

Insulation resistance:>100 MW (DC 500V);

Withstand voltage: 2000v, 50/60 Hz 1 min.

Contact electrical parameters

30VA, 1A (maximum), 380V (maximum)

Leakage rate

≤1X10-9 Pa.m3/s (Helium leakage inspection)

Connection thread

Female M24*1.5 (customizable)

Bourdon tube

All S.S 316L (Imported from Germany)

Movement

All S.S 316L (Imported from Germany)

Case

S.S 304

Window

Safety glass

Degree of protection

IP65

Dial

Aluminum (customizable logo)

Pointer

Aluminum, black


HGS60J
These instruments are used to monitor the density of SF6 gas in sealed tanks and can be widely used in medium voltage switchgear and RMU. They can provide multiple solutions to support new substations and the intelligent transformation of existing substations.
  • Nominal size: 64mm

  • Leakage rate: ≤1X10-9 Pa.m3/s (Helium leakage inspection)

  • Connection thread: Female M24*1.5 (customizable)

  • Accuracy class: At 20℃:1.0 or 1.6;-40℃ to +60℃:2.5


Get A Free Quote